Panasonic ECOi Systems: How the Codes Read
Panasonic ECOi systems show an alarm as a letter and two digits (E04, P29) on the wired remote controller and on the outdoor unit LEDs. In these manuals the letter groups the alarms: E codes are communication and address alarms, F codes sensors and memory, H codes compressor current, oil and the HIC, L codes settings and the 4-way valve, and P codes protective devices.
The outdoor unit shows the same alarm on two red LEDs: LED 1 blinks M times for the family (2 for P, 3 for H, 4 for E, 5 for F, 6 for L), then LED 2 blinks N times for the number, and the cycle repeats. Two blinks then seventeen blinks is P17. The 2-way and Mini ECOi lists share most codes but not all meanings: P05 is compressor 1 open phase detection on a 2-way system and a power supply error on a Mini ECOi, so check the outdoor unit model first.
This guide covers the Panasonic ECOi 2-way VRF outdoor unit alarm codes (8 to 16 HP) and the Mini ECOi alarm codes, from two Panasonic service manuals for European 50 Hz models (U-8ME2E8 and U-4LE1E5). Every meaning below is Panasonic’s own. Panasonic residential split codes are a different list and are not covered here.
Search all 88 Panasonic codes · Run Panasonic on AirNexus
Communication and Address Faults (E Codes)
E codes are communication and address faults: between the remote controller, the indoor units and the outdoor units, and during auto address setting.
Know about E06 before the tenant does.
A Nexus controller sits on the system's control network and logs every fault the moment it happens: the code, the unit address, and the time. It lands in the AirNexus app before anyone calls you.
Protection Faults (P Codes)
P codes are protective device activations: discharge temperature, high pressure, open phase, overcurrent, the outdoor fans and compressor start-up. On the 2-way manual, compressor 2 codes apply to 14 and 16 HP units, which have two inverter compressors.
Compressor Current and Oil Faults (H Codes)
H codes cover compressor current, CT sensors, discharge sensors, low pressure, oil and the HIC.
Sensor and Memory Faults (F Codes)
F codes are temperature and pressure sensor faults and the outdoor unit memory. The sensor tag in brackets matches the board marking.
Setting Faults (L Codes)
L codes are outdoor unit settings and the 4-way valve.
What Nexus iQ Shows Alongside the Code
A fault code tells you what tripped. On a Nexus 8, 16 or 32, Nexus iQ reads the Panasonic system’s own data off its control line, so you can see the readings around a code before anyone goes to site. What you see depends on what the system reports.
| When you see | The code tells you | In Nexus iQ |
|---|---|---|
| E06, E04 | Indoor and outdoor units have lost each other | Push notification with the unit address and time. Diagnostics marks a reading that has stopped updating as stale, with its age. |
| P04, P20 | High pressure switch or high load | High and low pressure live in Diagnostics, charted in Trends from 6 hours to 30 days. |
| P03 | Compressor discharge temperature error | Discharge temperature live, charted in Trends to see what led up to it. |
| H01, P29 | Compressor overcurrent or start failure | Compressor frequency and power draw live, with a Health score per unit over 24 hours, 7 days or 30 days. |
The same faults reach the free AirNexus app as push notifications. See Nexus iQ.
Quick Reference: Every Panasonic ECOi Code in This Guide
Search by code or keyword. The System column tells you which list a code comes from.
| Code | System | Alarm meaning | Manual page |
|---|---|---|---|
| E06 | ECOi 2-way | Outdoor unit receiving failure from indoor unit | 6-5 to 6-6 |
| E12 | ECOi 2-way | Prohibit starting auto address setting | 6-5 to 6-6 |
| E15 | ECOi 2-way | Auto address alarm (a small number of indoor units) | 6-5 to 6-6 |
| E16 | ECOi 2-way | Auto address alarm (a large number of indoor units) | 6-5 to 6-6 |
| E20 | ECOi 2-way | No indoor unit during auto address setting | 6-5 to 6-6 |
| E24 | ECOi 2-way | Receiving failure of relay control unit from outdoor unit(s) | 6-5 to 6-6 |
| E25 | ECOi 2-way | Failure of outdoor unit address setting (duplicative) | 6-5 to 6-6 |
| E26 | ECOi 2-way | Inconsistencies in number of outdoor units | 6-5 to 6-6 |
| E29 | ECOi 2-way | Failure of outdoor unit to receive relay control unit | 6-5 to 6-6 |
| E31 | ECOi 2-way | Wiring error between the P.C. boards ([L-Pow], [HIC] wire) | 6-5 to 6-6 |
| F04 | ECOi 2-way | Compressor 1 discharge temperature sensor abnormal (DISCH1) | 6-5 to 6-6 |
| F05 | ECOi 2-way | Compressor 2 discharge temperature sensor abnormal (DISCH2) | 6-5 to 6-6 |
| F06 | ECOi 2-way | Outdoor unit heat exchanger 1 gas (inlet) temperature sensor abnormal (EXG1) | 6-5 to 6-6 |
| F07 | ECOi 2-way | Outdoor unit heat exchanger 1 liquid (outlet) temperature sensor abnormal (EXL1) | 6-5 to 6-6 |
| F08 | ECOi 2-way | Outdoor temperature sensor abnormal (TO) | 6-5 to 6-6 |
| F12 | ECOi 2-way | Compressor inlet temperature sensor abnormal (SCT) | 6-5 to 6-6 |
| F14 | ECOi 2-way | Supercooling gas temperature sensor abnormal (SCG) | 6-5 to 6-6 |
| F16 | ECOi 2-way | High pressure sensor abnormal, high-load (HPS) | 6-5 to 6-6 |
| F17 | ECOi 2-way | Low pressure sensor abnormal (LPS) | 6-5 to 6-6 |
| F23 | ECOi 2-way | Outdoor unit heat exchanger 2 gas (inlet) temperature sensor abnormal (EXG2) | 6-5 to 6-6 |
| F24 | ECOi 2-way | Outdoor unit heat exchanger 2 liquid (outlet) temperature sensor abnormal (EXL2) | 6-5 to 6-6 |
| F31 | ECOi 2-way | Outdoor unit nonvolatile memory (EEPROM) error | 6-5 to 6-6 |
| H01 | ECOi 2-way | Compressor 1 abnormal current values (overcurrent) | 6-5 to 6-6 |
| H11 | ECOi 2-way | Compressor 2 abnormal current values (overcurrent) | 6-5 to 6-6 |
| H03 | ECOi 2-way | Compressor 1 CT sensor disconnected, short-circuit | 6-5 to 6-6 |
| H05 | ECOi 2-way | Compressor 1 discharge temperature sensor disconnected | 6-5 to 6-6 |
| H06 | ECOi 2-way | Low pressure abnormal lowering | 6-5 to 6-6 |
| H07 | ECOi 2-way | Oil loss error | 6-5 to 6-6 |
| H08 | ECOi 2-way | Oil sensor (connection) error 1 | 6-5 to 6-6 |
| H13 | ECOi 2-way | Compressor 2 CT sensor disconnected, short-circuit | 6-5 to 6-6 |
| H15 | ECOi 2-way | Compressor 2 discharge temperature sensor disconnected | 6-5 to 6-6 |
| H27 | ECOi 2-way | Oil sensor (connection) error 2 | 6-5 to 6-6 |
| H31 | ECOi 2-way | Compressor 1 HIC alarm | 6-5 to 6-6 |
| H21 | ECOi 2-way | Compressor 2 HIC alarm | 6-5 to 6-6 |
| L04 | ECOi 2-way | Outdoor unit address settings duplicated | 6-5 to 6-6 |
| L10 | ECOi 2-way | Outdoor unit capacity settings not made | 6-5 to 6-6 |
| L17 | ECOi 2-way | Inconsistencies in outdoor unit models | 6-5 to 6-6 |
| L18 | ECOi 2-way | 4-way valve coil disconnected, line disconnected | 6-5 to 6-6 |
| P03 | ECOi 2-way | Compressor 1 discharge temperature error | 6-5 to 6-6 |
| P04 | ECOi 2-way | Actuation of high pressure switch | 6-5 to 6-6 |
| P05 | ECOi 2-way | Compressor 1 open phase detection | 6-5 to 6-6 |
| P15 | ECOi 2-way | Compressor 2 open phase detection | 6-5 to 6-6 |
| P14 | ECOi 2-way | Actuation of O2 sensor | 6-5 to 6-6 |
| P16 | ECOi 2-way | Compressor 1 secondary overcurrent | 6-5 to 6-6 |
| P26 | ECOi 2-way | Compressor 2 secondary overcurrent | 6-5 to 6-6 |
| P17 | ECOi 2-way | Compressor 2 discharge temperature error | 6-5 to 6-6 |
| P20 | ECOi 2-way | High load (forgot to open valves) | 6-5 to 6-6 |
| P22 | ECOi 2-way | Outdoor unit fan 1 failure (IPM damage, overcurrent, inverter failure, DC fan lock, Hall IC open phase) | 6-5 to 6-6 |
| P24 | ECOi 2-way | Outdoor unit fan 2 failure (IPM damage, overcurrent, inverter failure, DC fan lock, Hall IC open phase) | 6-5 to 6-6 |
| P29 | ECOi 2-way | Compressor 1 start failure (compressor lock, compressor wiring open phase, DCCT failure) | 6-5 to 6-6 |
| P19 | ECOi 2-way | Compressor 2 start failure (compressor lock, compressor wiring open phase, DCCT failure) | 6-5 to 6-6 |
| E01 | Mini ECOi | Remote controller reception error | 5-5 to 5-6 |
| E02 | Mini ECOi | Remote controller transmission error | 5-5 to 5-6 |
| E03 | Mini ECOi | Error in indoor unit receiving signal from remote controller (central) | 5-5 to 5-6 |
| E04 | Mini ECOi | Error in indoor unit receiving signal from the outdoor unit | 5-5 to 5-6 |
| E05 | Mini ECOi | Error in indoor unit transmitting signal to the outdoor unit | 5-5 to 5-6 |
| E06 | Mini ECOi | Error in the outdoor unit receiving signal from the indoor unit | 5-5 to 5-6 |
| E07 | Mini ECOi | Error in outdoor unit transmitting signal to the indoor unit | 5-5 to 5-6 |
| E08 | Mini ECOi | Duplicate indoor unit address settings error | 5-5 to 5-6 |
| E09 | Mini ECOi | More than one remote controller set to main error | 5-5 to 5-6 |
| E12 | Mini ECOi | Start of auto address setting prohibited due to auto address setting being in progress | 5-5 to 5-6 |
| E13 | Mini ECOi | Error in indoor unit transmitting signal to remote controller | 5-5 to 5-6 |
| E15 | Mini ECOi | Auto-address alarm (not enough units) | 5-5 to 5-6 |
| E16 | Mini ECOi | Auto-address alarm (too many units) | 5-5 to 5-6 |
| E18 | Mini ECOi | Faulty communication in group control wiring | 5-5 to 5-6 |
| E20 | Mini ECOi | No indoor units error | 5-5 to 5-6 |
| E30 | Mini ECOi | Outdoor unit serial transmission error | 5-5 to 5-6 |
| F04 | Mini ECOi | Compressor discharge temperature sensor error | 5-5 to 5-6 |
| F07 | Mini ECOi | Heat exchanger inlet temperature sensor (C1) error | 5-5 to 5-6 |
| F08 | Mini ECOi | Outdoor air temperature sensor (TO) error | 5-5 to 5-6 |
| F12 | Mini ECOi | Compressor intake temperature sensor (TS) error | 5-5 to 5-6 |
| F16 | Mini ECOi | High pressure sensor error | 5-5 to 5-6 |
| F31 | Mini ECOi | Outdoor unit nonvolatile memory (EEPROM) error | 5-5 to 5-6 |
| H01 | Mini ECOi | Primary current (input) detect of overcurrent | 5-5 to 5-6 |
| H02 | Mini ECOi | PAM error | 5-5 to 5-6 |
| H03 | Mini ECOi | Compressor CT sensor (current sensor) unplugged | 5-5 to 5-6 |
| H31 | Mini ECOi | HIC error | 5-5 to 5-6 |
| L04 | Mini ECOi | Duplicated setting of outdoor system address error | 5-5 to 5-6 |
| L10 | Mini ECOi | Outdoor unit capacity not yet set up error | 5-5 to 5-6 |
| L18 | Mini ECOi | 4-way valve operation failure | 5-5 to 5-6 |
| P03 | Mini ECOi | Compressor discharge temperature error | 5-5 to 5-6 |
| P04 | Mini ECOi | Actuation of high pressure switch | 5-5 to 5-6 |
| P05 | Mini ECOi | Power supply error | 5-5 to 5-6 |
| P13 | Mini ECOi | Forgot-to-open valve alarm | 5-5 to 5-6 |
| P14 | Mini ECOi | O2 sensor | 5-5 to 5-6 |
| P16 | Mini ECOi | Overcurrent of inverter compressor | 5-5 to 5-6 |
| P22 | Mini ECOi | Outdoor fan motor error | 5-5 to 5-6 |
| P29 | Mini ECOi | INV compressor start-up failed (including lock) due to INV compressor wiring open phase, faulty DCCT, etc. | 5-5 to 5-6 |
Run Panasonic on AirNexus
AirNexus supplies the controls and your HVAC contractor installs them. One app covers every unit on the site.
Not sure which fits? Find your system. AirNexus supplies Australia and New Zealand; distributors and project teams elsewhere can register as a partner.
Sources
The alarm codes and outdoor LED display in this guide are drawn from the following Panasonic service manuals for European models.
- Panasonic U-8ME2E8 Service Manual & Test Run Service Manual (2WAY system, R410A), Trouble Diagnosis: 2WAY Alarm Codes
- Panasonic U-4LE1E5 Mini VRF System Service Manual, Trouble Diagnosis: Mini VRF System Alarm Codes
Panasonic fault codes: frequently asked questions
What does Panasonic error code E04 mean?
On Panasonic Mini ECOi, E04 is an error in the indoor unit receiving the signal from the outdoor unit. Its partner codes are E05 (indoor unit transmitting to the outdoor unit), E06 (outdoor unit receiving from the indoor unit) and E07 (outdoor unit transmitting to the indoor unit). See the E04 entry.
What does Panasonic error code P29 mean?
P29 is a compressor start failure. The ECOi 2-way manual lists compressor lock, an open phase in the compressor wiring and a DCCT failure; on 14 and 16 HP units, P19 is the same fault on compressor 2. See the P29 entry.
How do I read a Panasonic alarm on the outdoor unit LEDs?
Count the blinks. LED 1 blinks the family (2 for P, 3 for H, 4 for E, 5 for F, 6 for L), then LED 2 blinks the alarm number, and the cycle repeats. Two blinks then sixteen blinks is P16.
Can I see Panasonic fault codes remotely?
Yes. A Nexus 8, 16 or 32 on the Panasonic central control line sends each fault to the free AirNexus app as a push notification, with the unit address and the time it happened. Nexus iQ lists it in Findings & Insights, and the Diagnostics view shows the system’s live readings around it. See VRF control.