We won the 2026 iAwards Queensland Industrial Technology category.Read more →
← Back to The Feed
TECHNICAL 15 min read · Updated

Daikin VRV Fault Codes: The Field Guide

Daikin VRV error codes from Daikin’s own service manuals. What each code means, what to check first and the common cause. Built for Australian HVAC contractors on site.

Daikin VRV Systems: How the Codes Read

Daikin VRV systems report a fault as a letter-and-number code (U4, E3, L5) on the remote controller. Each entry below gives what the code means, what to check first and the common cause, drawn from Daikin’s VRV service manuals.

Working on a Daikin split system or a Sky Air ducted unit? Those codes are a separate list: see Daikin split system and ducted error codes.

Daikin VRV fault codes fall into five main categories, and understanding the prefix tells you immediately which system is involved:

U codes: communication, refrigerant and power supply faults
E codes: outdoor PCB, pressure and protection faults
L codes: compressor and inverter faults
A codes: indoor unit faults (PCB, drain, fan, capacity adapter)
F, H and J codes: refrigerant circuit and sensor faults

For licensed technicians. This guide is general information to help you find the right part of the manufacturer’s service manual. Isolate power before opening any unit, follow the manufacturer’s procedures, and leave refrigerant work to a licensed refrigerant technician (in Australia, an ARC licence holder).

Search all 24 Daikin codes · Run Daikin on AirNexus

U Codes (U4, U9, U0): Communication, Refrigerant and Power Faults

U codes on VRV systems cover three different things: transmission faults on the F1-F2 (DIII-NET) line (U4, U9, UA, UF), a refrigerant shortage (U0), and a power supply abnormality (U2). Most of the transmission faults come back to wiring: a loose lug, a crossed pair, or a short between F1-F2 and a power leg.

U0
Refrigerant shortage
What it means
The outdoor unit has detected the refrigerant shortage signature: low pressure on the suction line with high superheat at the outdoor coil sensors. The system stops to protect the compressor.
What to check first
Confirm the calculated charge against the piping-length figure for the run, then leak test and weigh in refrigerant if it is low. Check that both stop valves are fully open, since a partly open valve mimics low charge. Rule out a faulty thermistor or high pressure sensor, because the U0 logic relies on those readings. On long runs, recalculate the charge for piping length rather than trusting the nameplate value.
Common cause
A sustained refrigerant shortage that repeats U0 on every run. Also common where the charge was never corrected for a long piping run, so the simple nameplate value left the system short.
In Nexus iQ. The fault shows in Findings as a plain-English sentence, with how long it has been active.
↓ Back to search
U2
Power supply abnormality or instantaneous power failure
What it means
The outdoor unit has detected an out-of-band supply: no zero-cross within 10 seconds, a DC bus voltage drop below 150 to 180 V, or a DC bus over-voltage. The compressor is held off and the system retries after 3 minutes.
What to check first
Measure phase-to-phase and phase-to-neutral at the outdoor terminals. Imbalance must stay under 10% with no frequency drift. If U2 followed a known site brownout or outage, allow the unit to self-restart after the 3-minute stand-by; no hardware action is needed once the supply has stabilised. If it recurs, discharge the DC bus and verify before any connector work, then inspect the DC voltage detection circuit and the inverter main capacitors for a bulge or leak.
Common cause
A faulty supply or phase imbalance at the outdoor terminals. Also a momentary site outage: if U2 clears on the 3-minute timer and the supply has stabilised, no hardware action is required.
In Nexus iQ. Compressor frequency, current and fan speed are read live where the system reports them, and Health scores each unit over 24 hours, 7 days or 30 days.
↓ Back to search
U4
Transmission abnormality between indoor and outdoor
What it means
The VRV system has lost transmission between the indoor units and the outdoor bank over the F1-F2 (DIII-NET) line. The affected indoor units stop until transmission is restored.
What to check first
Trace F1-F2 from each indoor back to the master outdoor and reterminate any loose lug. F1 and F2 are non-polarised, but a short to a power leg is fatal: it takes out the DIII-NET driver on both indoor and outdoor PCBs. Confirm the outdoor unit is powered up and its service LED is blinking at regular intervals, because without outdoor power every indoor on the system reports U4. Cross-check indoor and outdoor address settings, and run auto-address from the outdoor once transmission is restored.
Common cause
A loose or crossed F1-F2 termination, or the transmission line routed alongside power cabling causing noise injection. The outdoor unit left unpowered. An address mismatch after indoor units were added or moved.
In the AirNexus app. On a Nexus 8, 16 or 32 this code arrives as a push notification with the unit address and the time it happened, and Nexus iQ Diagnostics shows the raw data straight off the bus.
↓ Back to search
U9
Transmission fault from another indoor unit in the same system
What it means
The indoor unit reporting U9 has detected a malfunction signal from another indoor unit in the same system. The unit reporting U9 is not itself faulty: it stops while the originating unit is in fault.
What to check first
Wait at least 2 minutes after U9 first appears, then walk every other indoor on the system and read its current code. The originating unit usually carries the primary fault, often a U4 transmission fault or an expansion valve fault; repair that first and the U9 on the neighbours clears after. Test F1-F2 wiring between every indoor and the outdoor, and cross-check addresses if units were recently added or moved.
Common cause
Another indoor unit on the same system is in fault, typically a transmission fault or an expansion valve fault. The unit showing U9 is only reporting the knock-on, so servicing the originating unit clears it.
In the AirNexus app. On a Nexus 8, 16 or 32 this code arrives as a push notification with the unit address and the time it happened, and Nexus iQ Diagnostics shows the raw data straight off the bus.
↓ Back to search
UA
Improper combination of indoor unit and remote controller
What it means
The outdoor unit has detected a transmission abnormality consistent with mismatched indoor or outdoor models, or wrong inter-unit wiring. The system halts.
What to check first
Trace the indoor-outdoor wiring and reterminate any loose lug, verifying F1-F2 against the diagram; a wrong-polarity termination on some controllers throws UA on first power-on. Cross-check the indoor and outdoor model pairing against the official combination list and replace any unit that is not listed. Mixing R32 and R410A units in one system always throws UA. Confirm the wired remote is one of the models listed for the indoor.
Common cause
Wrong inter-unit wiring, or an indoor and outdoor pairing that is not an approved combination. A remote controller that is not compatible with the indoor unit.
In the AirNexus app. On a Nexus 8, 16 or 32 this code arrives as a push notification with the unit address and the time it happened, and Nexus iQ Diagnostics shows the raw data straight off the bus.
↓ Back to search
UF
Wiring and piping mismatch
What it means
During check operation, the number of indoor units seen on the transmission line does not match the number that responded to a temperature change. The system will not run until check operation completes.
What to check first
Walk the system from each indoor back to the outdoor and confirm the F1-F2 transmission line and the refrigerant pair go to the same indoor; re-pair where crossed. Crossed liquid and gas lines with correct wiring will also throw UF. Open all liquid and gas stop valves on every outdoor module. Then run check operation from the master outdoor: press and hold the RESET button for 5 seconds and allow up to 12 minutes; the system will not run during that window.
Common cause
Indoor-outdoor wiring or refrigerant piping crossed between two indoor units, so the wiring pair and the pipe pair no longer match. A single stop valve left closed. Check operation not run.
In the AirNexus app. On a Nexus 8, 16 or 32 this code arrives as a push notification with the unit address and the time it happened, and Nexus iQ Diagnostics shows the raw data straight off the bus.
↓ Back to search
The same fault, on your phone

Know about U0 before the tenant does.

A Nexus controller sits on the system's control network and logs every fault the moment it happens: the code, the unit address, and the time. It lands in the AirNexus app before anyone calls you.

Supplied by AirNexus to HVAC partners across Australia and New Zealand. Become a partner

E Codes (E3, E4, E7): PCB, Pressure and Protection Faults

E codes on VRV cover the outdoor PCB (E1), the high and low pressure switch trips (E3, E4), compressor motor lock or overheat (E5), and the outdoor fan motor (E7). The trap with the pressure and protection trips is telling a genuine out-of-range condition apart from a switch or sensor that has failed, so confirm the reading before you condemn hardware.

E1
Outdoor unit PCB abnormality
What it means
The outdoor main PC board on the VRV outdoor module has logged an internal hardware fault. The system stops and the code is reported on the wired remote and the outdoor PCB seven-segment display.
What to check first
Measure phase-to-phase and phase-to-neutral at the outdoor terminals; imbalance must stay under 10% with no frequency drift. Verify the capacity adapter fitted to the outdoor PCB matches the unit, and meter the outdoor fan motor windings against the manual. If E1 clears on a power reset and returns intermittently, sweep nearby plant for VSD, RF or paging-system noise and confirm the earthing is solid. Replace the outdoor main PCB only after supply, capacity adapter, fan motor and noise sources have been ruled out.
Common cause
A faulty supply or phase imbalance, or a capacity adapter that does not match the unit. External electrical noise injected onto a clean-tested board. The outdoor main PC board itself only after the rest has been ruled out.
In Nexus iQ. Compressor frequency, current and fan speed are read live where the system reports them, and Health scores each unit over 24 hours, 7 days or 30 days.
↓ Back to search
E3
Activation of high pressure switch
What it means
The outdoor unit has tripped on high pressure: the high pressure switch opened above 4,170 kPa (41.7 bar / 605 psi), or high pressure control above 3,800 kPa (38 bar / 551 psi) was hit 16 times within 300 minutes. The unit halts.
What to check first
Inspect the outdoor coil for leaf litter, dust and damaged fins and clean it from the inside out, then confirm the fan reaches commanded speed once airflow is restored. Walk the outdoor and confirm both stop valves are fully open, because a back-seated valve trips E3 within seconds of compressor start. Test the high pressure switch: it must be closed at idle pressure, so replace it if it sits open or chatters. If the high side runs hot for the saturated temperature, suspect non-condensables or an overcharge; recover, weigh the charge against the nameplate and reduce to the nameplate value.
Common cause
A blocked or dirty outdoor coil, or insufficient outdoor airflow. A closed or back-seated stop valve. A refrigerant overcharge or non-condensables in the refrigerant, which is a common cause of repeated E3 events on this platform.
In Nexus iQ. The outdoor unit’s pressures and temperatures are read live where the system reports them. Chart them in Trends, from the past 6 hours to 30 days, to see what led up to this code.
↓ Back to search
E4
Activation of low pressure switch
What it means
The VRV outdoor unit has stopped because the low pressure sensor read below 230 kPa (2.3 bar / 33 psi) through the protection window, or evaporating temperature fell below the trip line.
What to check first
Inspect the low pressure sensor cable for chafing and seating at the outdoor PCB, and reseat or replace it where continuity fails, before condemning the sensor. Confirm the calculated charge for the piping length and weigh in if it is low, since a sustained shortage repeats E4 on restart. Check every indoor on the system for a filter, grille or coil restriction, because one starved indoor can pull the whole bank into E4 in heating. Verify every stop valve is fully open, and read low pressure on the wired remote against a manifold gauge to confirm the sensor.
Common cause
A refrigerant shortage, or a low pressure sensor cable that has chafed or come loose. Blocked indoor airflow on one or more units. A closed or partly open stop valve.
In Nexus iQ. The fault shows in Findings as a plain-English sentence, with how long it has been active.
↓ Back to search
E5
Compressor motor lock or overheat
What it means
The VRV outdoor inverter has detected that the inverter compressor is not turning at the commanded electrical speed. On 14 to 20 hp classes the code reports for compressor 1 or 2; use monitor mode on the outdoor PCB to identify which.
What to check first
Walk the outdoor and confirm both stop valves are fully open before any compressor work, because a closed liquid valve presents as compressor lock. Mark and disconnect the U, V and W leads at the compressor terminals and verify each phase against the wiring diagram; a swapped phase reads as lock on first start. Meter U-V-W to ground and between phases against the manual. If non-condensables or moisture are suspected, recover, evacuate to a deep vacuum and recharge with virgin refrigerant. Discharge the DC bus and verify with a meter before any connector work on the inverter board.
Common cause
A closed compressor stop valve, or a U, V and W phase connected out of order. Refrigerant contamination. A faulty inverter board or compressor, but only after wiring, valves and charge have been ruled out.
In Nexus iQ. Compressor frequency, current and fan speed are read live where the system reports them, and Health scores each unit over 24 hours, 7 days or 30 days.
↓ Back to search
E7
Outdoor fan motor abnormality
What it means
The VRV outdoor PCB has detected the outdoor fan motor is locked, has lost feedback, or is drawing locked-rotor current. The system halts to protect the motor and inverter.
What to check first
Inspect the fan motor harness for chafing and the connector at the outdoor PCB for spread or corroded pins, then reseat firmly, since a loose connector throws E7 intermittently in damp weather. Power off and rotate the outdoor fan by hand to clear any obstruction. Disconnect the motor and meter the windings against the manual, replacing it if the windings are open, shorted to frame or out of band. On heat pump platforms, low charge can drag the fan into protection, so confirm the calculated charge if the mechanicals check out.
Common cause
A chafed fan motor harness or a loose, corroded connector at the outdoor PCB. A failed outdoor fan motor, or an obstruction in the fan. On heat pump systems, a refrigerant shortage pulling the fan into protection.
In Nexus iQ. Compressor frequency, current and fan speed are read live where the system reports them, and Health scores each unit over 24 hours, 7 days or 30 days.
↓ Back to search

L Codes (L1, L5, LC): Compressor and Inverter Faults

L codes sit on the compressor and inverter, the most expensive components in the outdoor unit. Not every L code means a compressor replacement: L4 (inverter radiating fin temperature) and some L1 trips come back to supply, charge or airflow, and clear once the external cause is corrected. Discharge the DC bus and verify with a meter before any connector work on these boards.

L1
Outdoor main PCB abnormality
What it means
The VRV outdoor inverter PC board has detected an internal hardware fault: a failed power transistor, a blown fuse, or a failed gate driver. The system halts.
What to check first
Discharge the DC bus and verify with a meter before any connector work. Measure phase-to-phase and phase-to-neutral at the outdoor terminals; imbalance must stay under 10%. Megger each outdoor fan motor to ground, since a failed fan can take the inverter board with it on the next start. Mark and disconnect each compressor phase and meter U-V-W to ground and between phases; a short to ground pops the inverter the moment power returns. Inspect the inverter board fuse for a blow signature and replace it with the rated spare. Replace the board only after supply, fans and compressor wiring have been ruled out.
Common cause
A faulty supply or phase imbalance. A failed outdoor fan motor, or a compressor winding shorted to ground that takes the board with it. A blown inverter fuse, which points to a downstream short rather than the board alone.
In Nexus iQ. Compressor frequency, current and fan speed are read live where the system reports them, and Health scores each unit over 24 hours, 7 days or 30 days.
↓ Back to search
L4
Inverter radiating fin temperature abnormality
What it means
The outdoor inverter heat sink (radiating fin) temperature is above its protection threshold. The unit halts to protect the inverter power transistors.
What to check first
Spin the outdoor fan by hand and confirm free rotation, then meter the windings against the manual; a stalled fan is the most direct cause of L4. Inspect the inverter compartment for a dust mat, foreign matter or modified ducting restricting airflow across the heat sink, and clean it. Power off and inspect the heat sink to inverter interface: refresh the thermal paste if it is dried, missing or contaminated, and re-torque the mounting screws in the prescribed sequence. Meter the radiating fin thermistor against the published characteristic and replace it if it is out of band.
Common cause
A faulty or stalled outdoor fan motor. Restricted heat sink airflow from dust or foreign matter. Silicone grease at the heat sink that has dried out or gone missing. A radiating fin thermistor reading out of band.
In Nexus iQ. Compressor frequency, current and fan speed are read live where the system reports them, and Health scores each unit over 24 hours, 7 days or 30 days.
↓ Back to search
L5
Inverter instantaneous overcurrent (AC output)
What it means
The VRV outdoor inverter has measured instantaneous overcurrent on the AC output to the compressor. The unit halts to prevent damage to the inverter and compressor.
What to check first
Discharge the DC bus and verify with a meter before connector work. Megger the compressor windings to ground and meter U-V-W phase resistance; replace the compressor only after wiring, the expansion valve and the inverter board have been ruled out. Measure phase-to-phase voltage at the outdoor terminals, with imbalance under 10%. Power off, isolate, then attempt to spin the compressor shaft where the manual allows, since a mechanically locked compressor throws L5 on first start.
Common cause
A compressor winding fault, a mechanically locked compressor, or a faulty supply or phase imbalance. The inverter board only after the compressor and supply have been ruled out.
In Nexus iQ. Compressor frequency, current and fan speed are read live where the system reports them, and Health scores each unit over 24 hours, 7 days or 30 days.
↓ Back to search
LC
Transmission error between inverter and control PC boards
What it means
The VRV outdoor unit has lost the internal handshake between the control PC board and the inverter PC board. The system halts because compressor commands cannot be confirmed.
What to check first
Discharge the DC bus and verify with a meter before any connector work. Reseat the harness between the control and inverter boards at both ends, and inspect each connector for spread pins or oxidation, since a vibration-loosened pin throws LC after warm runtime. Replace the harness if any core is broken or the insulation has chafed. If LC clears on a power reset and recurs, sweep nearby plant for VSD, RF or paging-system noise and confirm the earthing is solid. Swap one board at a time only after the harness has been confirmed good.
Common cause
A loose or damaged harness between the control and inverter boards, or a spread pin at either connector. External electrical noise. A faulty board only after the harness has been confirmed good.
In the AirNexus app. On a Nexus 8, 16 or 32 this code arrives as a push notification with the unit address and the time it happened, and Nexus iQ Diagnostics shows the raw data straight off the bus.
↓ Back to search

A, F, H and J Codes (A3): Indoor, Refrigerant and Sensor Faults

These codes cover the indoor units (A1 PCB, A3 drain, A6 fan, AH capacity adapter), the refrigerant circuit (F3 discharge temperature, F6 high pressure or overcharge), and the outdoor thermistors (H9, J3, J6).

A1
Indoor unit PCB abnormality
The indoor unit main PCB cannot store or read its internal settings, or has detected a hardware fault during self-check. The unit halts until power is recycled or the board corrected. Reseat every terminal at the indoor unit and check the supply against the nameplate (imbalance under 10%), then power-cycle. Confirm the indoor and outdoor pairing is an approved combination before condemning the board. A power hit can also trigger A1 as a one-off noise event.
↓ Back to search
A3
Drain level control system abnormality
The indoor float switch on the S1L circuit has signalled a high water level and the unit has stopped to protect the drain pan. Check the drain pump runs when commanded and pulls water from the pan, and verify the drain run has continuous fall with no traps or blockage. Test the float switch for continuity and reseat the X8A connector. If no field drain pump kit is fitted, the X15A short-circuit jumper must be present and continuous.
↓ Back to search
A6
Indoor unit fan motor lock or overload
The indoor PCB has detected the fan motor stalled, lost feedback, or drew excessive current, and the unit has halted. Power off and rotate the fan by hand to confirm it spins freely and clear any debris or transit packing fouling the impeller. Inspect the fan motor harness back to the indoor PCB, reseat the connector and replace any chafed wire. Disconnect the motor and check the windings for continuity and the rotor for free spin; replace the motor if the windings are open or shorted to frame.
↓ Back to search
AH
Capacity adapter or expansion valve motor type abnormality
The indoor unit reports that the capacity adapter is missing on a spare-part PCB, or that the expansion valve motor type set on the board does not match the fitted valve. The unit stops thermo until corrected. Confirm the expansion valve motor type setting (gear type versus direct drive) matches the fitted valve, then power reset. After fitting a spare-part indoor PCB, fit the matching capacity adapter onto the new board; recovery is automatic once it is in place.
↓ Back to search
F3
Discharge pipe temperature abnormality
The outdoor unit has detected discharge pipe temperature climbing above the protection threshold and has stopped to prevent compressor overheat damage. Low charge causes high superheat and high discharge temperature, so confirm the charge against the nameplate and weigh in after a leak test if it is short. Verify both stop valves are fully open, since a back-seated valve gives instant high discharge temperature on start. Confirm the expansion valve steps through its range, and meter the discharge pipe thermistor against the published characteristic.
↓ Back to search
F6
High pressure abnormality or refrigerant overcharge
The outdoor unit has logged the refrigerant overcharge signature: high discharge pressure with subcooling above the high band. The system halts and needs the charge corrected. Recover the system and weigh the actual charge against the nameplate, reducing it to the calculated charge. Before condemning the charge, reseat the outdoor air, deicer and subcool thermistor connectors at the outdoor PCB, because a floating thermistor reads below ambient and triggers F6. Compare the high pressure sensor reading on the wired remote against a manifold gauge.
↓ Back to search
F6 is the overcharge signature, not a spare high pressure switch. Before touching the charge, reseat the outdoor thermistor connectors: a floating thermistor reads below ambient and trips F6 on its own.
H9
Outdoor air thermistor abnormality
The outdoor air thermistor (R1T) input is outside the valid band, so the outdoor PCB cannot trust the ambient reading and the unit stops until the input recovers. Trace R1T from the air sample point to the outdoor PCB and confirm the connector is fully seated. Inspect the connector for green or black corrosion, common on coastal sites. Disconnect R1T and meter it against the published characteristic for the measured ambient, replacing it if out of band.
↓ Back to search
J3
Faulty outdoor discharge pipe thermistor
The outdoor discharge pipe thermistor reads out of band or below the heat exchanger temperature, so compressor discharge protection cannot run. Inspect the thermistor connector for spread or oxidised pins and reseat it. Identify the failed thermistor (R21T or R22T) in monitor mode on the outdoor PCB, disconnect it and meter against the manual's resistance and temperature characteristic, replacing it if out of band and re-clipping firmly to the tube with insulation refitted.
↓ Back to search
J6
Outdoor heat exchanger thermistor abnormality
The outdoor heat exchanging deicer thermistor (R7T) reads outside its valid range, so defrost control cannot run reliably and the unit halts. Inspect the thermistor connector for spread or oxidised pins and reseat it. Identify the failed thermistor in monitor mode on the outdoor PCB, disconnect R7T and meter against the manual's resistance and temperature characteristic, replacing it if out of band and re-clipping firmly to the tube with insulation refitted.
↓ Back to search

What Nexus iQ Shows Alongside the Code

A fault code tells you what tripped. On a Nexus 8, 16 or 32, Nexus iQ reads the Daikin system’s own data off its control line, so you can see the readings around a code before anyone goes to site. What you see depends on what the system reports.

When you seeThe code tells youIn Nexus iQ
U4, U9Transmission fault on the F1-F2 linePush notification with the unit address and time. Diagnostics marks a reading that has stopped updating as stale, with its age.
E3High pressure switch activatedHigh and low pressure live in Diagnostics, charted in Trends from 6 hours to 30 days.
E4, U0Low pressure switch or refrigerant shortageSuction temperature and low pressure live, charted in Trends.
L4, L5Inverter fin temperature or overcurrentCompressor frequency and power draw live, with a Health score per unit over 24 hours, 7 days or 30 days.

The same faults reach the free AirNexus app as push notifications. See Nexus iQ.

Daikin VRV Error Code List

Use this searchable table to quickly find any Daikin VRV fault code. Type a code (e.g., U4) or a keyword (e.g., pressure) to filter the results.

Daikin VRV error code list. Source: Daikin service documents (see Sources). From airnexus.io

Run Daikin on AirNexus

AirNexus supplies the controls and your HVAC contractor installs them. One app covers every unit on the site.

On site: SWOP Fortitude Valley runs its Daikin VRV on a Nexus 32. See the project →

Not sure which fits? Find your system. AirNexus supplies Australia and New Zealand; distributors and project teams elsewhere can register as a partner.

Sources

The fault code meanings and diagnostic steps in this guide are drawn from the following Daikin service manuals. The VRV manuals are the primary reference; the shared Daikin service manuals carry the same codes and corroborate the meanings.

Daikin fault codes: frequently asked questions

What does Daikin VRV error code U4 mean?

U4 is a transmission abnormality between the indoor and outdoor units on the F1-F2 (DIII-NET) line. The affected indoor units stop until transmission is restored. Start at the F1-F2 terminations and confirm the outdoor unit is powered: without outdoor power, every indoor unit on the system reports U4. See the U4 entry.

What does Daikin VRV error code U9 mean?

U9 means the indoor unit has detected a malfunction signal from another indoor unit in the same system. The unit showing U9 is not itself faulty: find the originating unit, usually carrying a U4 or an expansion valve fault, and repair that first. See the U9 entry.

Can I see Daikin VRV fault codes remotely?

Yes. A Nexus 8, 16 or 32 on the Daikin VRV central control line sends each fault to the free AirNexus app as a push notification, with the unit address and the time it happened. Nexus iQ lists it in Findings & Insights, and the Diagnostics view shows the system’s live readings around it. See VRF control.

Share this article

Got a Daikin site? Send us the job.

Tell us about the site and the system. We’ll come back with the AirNexus controls to suit.

Send us your job
Look up a codeSend us your job