Midea VRF Systems: Check the Series First
Midea has used different code lists across its VRF ranges, and the same code can mean different things on different series. On the current V8 range, codes have three characters (C21, P12, U38) and the indoor units have their own list (A11, C51, E24). The Atom T mini VRF and older V5 systems use two-character codes, and they do not always match: P9 is poor reversing of the four-way valve on an Atom T but fan module protection on a V5, and H4 is a repeated L0 fault on an Atom T but a repeated P6 fault on a V5. Read the model label on the outdoor unit before you look a code up.
The table holds 259 fault codes and 26 status hints. On the V8S, some codes need a manual restart to clear and are marked that way in the table. Codes starting with d are status hints, not faults: oil return, defrost and the refrigerant quantity checks.
This guide covers the Midea V8 series (V8S outdoor units and V8 indoor units), the Atom T mini VRF and the V5 heat recovery range, from Midea’s own service manuals. Every meaning below is the manual’s own. Midea residential split codes are a different list and are not covered here.
Search all 285 Midea codes · Run Midea on AirNexus
V8 Series: Communication and Setup Codes (C21)
Midea’s current V8 range uses three-character codes. C codes are communication faults and U codes are installation and setup checks, many of them raised during the test run.
Know about C21 before the tenant does.
A Nexus controller sits on the system's control network and logs every fault the moment it happens: the code, the unit address, and the time. It lands in the AirNexus app before anyone calls you.
V8 Series: Protection, Compressor and Drive Codes
Pressure, temperature and power protection on the V8S outdoor unit, and the compressor drive codes. Where a code starts with x, the x is the number of the compressor, fan or slave unit it refers to.
V8 Series: Indoor Unit Codes (A51)
Codes from the V8 indoor unit service manual.
Atom T Mini VRF Codes (P3, H4, H7)
The Atom T mini VRF uses two-character codes, shown on the outdoor unit.
V5 Series Codes for Older Systems (E0, E1, H4)
Older Midea V5 heat recovery systems use two-character codes that look like the Atom T codes but mean different things. Check the series before you look up E1, P3 or H4.
What Nexus iQ Shows Alongside the Code
A fault code tells you what tripped. On a Nexus 8, 16 or 32, Nexus iQ reads the Midea system’s own data off its control line, so you can see the readings around a code before anyone goes to site. What you see depends on what the system reports.
| When you see | The code tells you | In Nexus iQ |
|---|---|---|
| C21, C26 | Indoor unit lost from the master outdoor unit | Push notification with the unit address and time. Diagnostics marks a reading that has stopped updating as stale, with its age. |
| P12, P22 | High or low pressure protection | High and low pressure live in Diagnostics, charted in Trends from 6 hours to 30 days. |
| xF72 | Compressor discharge temperature protection | Discharge temperature live, charted in Trends to see what led up to it. |
| xL1E, xL5E | Compressor drive overcurrent or start-up failure | Compressor frequency and power draw live, with a Health score per unit over 24 hours, 7 days or 30 days. |
The same faults reach the free AirNexus app as push notifications. See Nexus iQ.
Midea VRF Error Code List
Search by code, series or keyword. The Series column tells you which list a code belongs to. Status hints are greyed out.
| Code | Series | Meaning | Manual page |
|---|---|---|---|
| A01 | V8S outdoor | Emergency shutdown | p.77 |
| AAx | V8S outdoor | No.x Inverter driver board does not match the main control board | p.77 |
| xA61 | V8S outdoor | No.x slave unit error | p.77 |
| xb53 | V8S outdoor | No.x Heat dissipation fan error | p.77, manual restart |
| C13 | V8S outdoor | The address of outdoor Unit is repeated | p.77 |
| C21 | V8S outdoor | Communication error between indoor and master outdoor unit | p.77 |
| C26 | V8S outdoor | Number of indoor units detected by master unit has decreased or less than the setting amount | p.77 |
| C28 | V8S outdoor | Number of indoor units detected by master unit has increased or more than the setting amount | p.77 |
| xC31 | V8S outdoor | Communication error between No.x slave outdoor unit and master outdoor unit | p.77 |
| C32 | V8S outdoor | Number of slave units detected by master unit has decreased | p.77 |
| C33 | V8S outdoor | Number of slave units detected by master unit has increased | p.77 |
| xC41 | V8S outdoor | Communication Error between main control board and No.x inverter driver board | p.77 |
| E41 | V8S outdoor | Outdoor ambient temperature sensor (T4) error (open/short) | p.77 |
| F31 | V8S outdoor | Microchannel heat exchanger outlet temperature sensor(T6B) error (open/short) | p.77 |
| F41 | V8S outdoor | Main heat exchanger pipe temperature sensor (T3) error (open/short) | p.77 |
| F51 | V8S outdoor | Microchannel heat exchanger inlet temperature sensor(T6A) error (open/short) | p.77 |
| F62 | V8S outdoor | Inverter driver board temperature (Tf) protection | p.77 |
| F63 | V8S outdoor | Non-inductive resistance temperature (Tr) protection | p.77 |
| F6A | V8S outdoor | F62 protection occurs 3 times in 100 minutes | p.77, manual restart |
| xF71 | V8S outdoor | No.(x) compressor discharge temperature sensor(T7C1/T7C2) error (open/short) | p.77, manual restart |
| xF72 | V8S outdoor | No.(x) compressor discharge temperature(T7C1/T7C2) protection | p.77 |
| F75 | V8S outdoor | Compressor discharge insufficient superheat protection | p.77 |
| F7A | V8S outdoor | F72 protection occurs 3 times in 100 minutes | p.77, manual restart |
| F81 | V8S outdoor | Gas pipe temperature sensor (Tg) error (open/short) | p.77 |
| F91 | V8S outdoor | Liquid pipe temperature sensor (T5) error (open/short) | p.77 |
| FA1 | V8S outdoor | Outdoor Heat exchanger gas temperature sensor (T8) error (open/short) | p.77 |
| FC1 | V8S outdoor | Outdoor heat exchanger liquid temperature sensor (TL) error (open/short) | p.77 |
| xFd1 | V8S outdoor | Compressor suction temperature sensor (T71/T72) error (open/short) | p.77 |
| FL1 | V8S outdoor | T10 outdoor ambient temperature sensor fault (open circuit/short circuit) | p.77 |
| P11 | V8S outdoor | High pressure sensor error | p.78 |
| P12 | V8S outdoor | High pressure protection | p.78 |
| P13 | V8S outdoor | High pressure switch protection | p.78 |
| P14 | V8S outdoor | P12 protection occurs 3 times in 60 minutes | p.78, manual restart |
| P21 | V8S outdoor | Low pressure sensor error | p.78, manual restart |
| P22 | V8S outdoor | Low pressure protection | p.78 |
| P24 | V8S outdoor | Abnormal rise of low pressure | p.78 |
| P25 | V8S outdoor | P22 protection occurs 3 times in 100 minutes | p.78, manual restart |
| xP32 | V8S outdoor | No.(x) compressor high DC bus current protection | p.78 |
| xP33 | V8S outdoor | XP32 protection occurs 3 times in 100 minutes | p.78, manual restart |
| P51 | V8S outdoor | High AC voltage protection | p.78 |
| P52 | V8S outdoor | Low AC voltage protection | p.78 |
| P53 | V8S outdoor | Phase B and N of the power cable are connected the opposite way | p.78, manual restart |
| P54 | V8S outdoor | DC bus low voltage protection | p.78 |
| P55 | V8S outdoor | DC bus ripple over protection | p.78, manual restart |
| xP56 | V8S outdoor | No.(x) Inverter driver board DC bus low voltage error | p.78, manual restart |
| xP57 | V8S outdoor | No.(x) Inverter driver board DC bus high voltage error | p.78, manual restart |
| xP58 | V8S outdoor | No.(x) Inverter driver board DC bus excessively high voltage error | p.78, manual restart |
| xP59 | V8S outdoor | No. (x) inverter module bus voltage drop fault | p.78 |
| P71 | V8S outdoor | EEPROM error | p.78, manual restart |
| Pb1 | V8S outdoor | HyperLink overcurrent error | p.78 |
| Pd1 | V8S outdoor | Anti-condensation protection | p.78 |
| Pd2 | V8S outdoor | Pd1 protection occurs 2 times in 60 minutes | p.78, manual restart |
| 1b01 | V8S outdoor | Electronic expansion valve (EEVA) error | p.78, manual restart |
| 2b01 | V8S outdoor | Electronic expansion valve (EEVB) error | p.78, manual restart |
| 3b01 | V8S outdoor | Electronic expansion valve (EEVC) error | p.78, manual restart |
| 4b01 | V8S outdoor | Electronic expansion valve (EEVE) error | p.78, manual restart |
| bA1 | V8S outdoor | HyperLink cannot control indoor unit’s electronic expansion valve | p.78 |
| U11 | V8S outdoor | Outdoor unit model is not set | p.79, manual restart |
| U12 | V8S outdoor | Outdoor unit Capacity setting error | p.79, manual restart |
| U21 | V8S outdoor | System contains the old Indoor Unit with old platforms | p.79, manual restart |
| U25 | V8S outdoor | Non-common Indoor Unit in the system | p.79, manual restart |
| U26 | V8S outdoor | Outdoor unit and Indoor Unit mismatch | p.79, manual restart |
| U31 | V8S outdoor | The test run was never successful, and did not run within 30 minutes after power-on | p.79, manual restart |
| U32 | V8S outdoor | Outdoor temperature out of operating range | p.79, manual restart |
| U33 | V8S outdoor | Indoor temperature out of operating range | p.79, manual restart |
| U34 | V8S outdoor | Outdoor and indoor temperature out of operating range | p.79, manual restart |
| U35 | V8S outdoor | Liquid side stop valve is not opened | p.79, manual restart |
| U37 | V8S outdoor | Gas side stop valve is not opened | p.79, manual restart |
| U38 | V8S outdoor | Outdoor unit has No address | p.79, manual restart |
| U3A | V8S outdoor | The refrigerant pipe connection is not consistent with the communication cable | p.79 |
| U3b | V8S outdoor | The installation environment is abnormal | p.79, manual restart |
| U3C | V8S outdoor | The VIP indoor unit is not set (valid in Changeover priority mode) | p.79 |
| U4x | V8S outdoor | Overconnection ratio contains U41-U48 | p.79, manual restart |
| U51 | V8S outdoor | Outdoor unit of Individual Series is installed in combined system. | p.79, manual restart |
| U53 | V8S outdoor | Different series of outdoor units are detected in the same VRF system. | p.79, manual restart |
| xL01 | V8S outdoor | XL1* or xL2* error occurs 3 times in 60 minutes | p.79, manual restart |
| xL1E | V8S outdoor | Hardware overcurrent | p.79 |
| xL11 | V8S outdoor | Software overcurrent | p.79 |
| xL12 | V8S outdoor | Software overcurrent protection last 30s | p.79 |
| xL2E | V8S outdoor | Module overtemperature protection | p.79 |
| xL33 | V8S outdoor | Bus voltage drop fault | p.79 |
| xL43 | V8S outdoor | The current sampling bias is abnormal | p.79 |
| xL45 | V8S outdoor | Motor code mismatch | p.79 |
| xL46 | V8S outdoor | IPM protection (FO) | p.79 |
| xL47 | V8S outdoor | Module type mismatch | p.79 |
| xL4E | V8S outdoor | EEPROM error | p.79 |
| xL5E | V8S outdoor | Startup failed | p.79 |
| xL51 | V8S outdoor | Out-of-step error | p.80 |
| xL52 | V8S outdoor | Locked-rotor protection | p.80 |
| xL6E | V8S outdoor | Compressor motor lack of phase protection | p.80 |
| xLBE | V8S outdoor | High pressure switch operation | p.80 |
| xLB7 | V8S outdoor | Other check exceptions | p.80 |
| xJ01 | V8S outdoor | XJ1* or xJ2* error occurs 10 times in 60 minutes | p.80, manual restart |
| xJ1E | V8S outdoor | Hardware overcurrent | p.80 |
| xJ11 | V8S outdoor | Software overcurrent | p.80 |
| xJ12 | V8S outdoor | Software overcurrent protection last 30s | p.80 |
| xJ2E | V8S outdoor | Module overtemperature protection | p.80 |
| xJ43 | V8S outdoor | The current sampling bias is abnormal | p.80 |
| xJ5E | V8S outdoor | Startup failed | p.80 |
| xJ51 | V8S outdoor | Out-of-step error | p.80 |
| xJ52 | V8S outdoor | Locked-rotor protection | p.80 |
| xJ6E | V8S outdoor | Motor lack of phase protection | p.80 |
| d0x | V8S outdoor (status) | Oil return,”x” is the current step node | p.80 |
| dfx | V8S outdoor (status) | Defrost, ”x” is the current step node | p.80 |
| d11 | V8S outdoor (status) | The outdoor ambient temperature exceeds the upper limit (Heating mode) | p.80 |
| d12 | V8S outdoor (status) | The outdoor ambient temperature exceeds the lower limit (Heating mode) | p.80 |
| d13 | V8S outdoor (status) | The outdoor ambient temperature exceeds the upper limit (Cooling mode) | p.80 |
| d14 | V8S outdoor (status) | The outdoor ambient temperature exceeds the lower limit (Cooling mode) | p.80 |
| d31 | V8S outdoor (status) | Refrigerant judgment: no result | p.80 |
| d32 | V8S outdoor (status) | Refrigerant quantity judgment:Significantly excessive | p.80 |
| d33 | V8S outdoor (status) | Refrigerant quantity judgment:Slightly excessive | p.80 |
| d34 | V8S outdoor (status) | Refrigerant quantity judgment:normal | p.80 |
| d35 | V8S outdoor (status) | Refrigerant quantity judgment:Slightly insufficient | p.80 |
| d36 | V8S outdoor (status) | Refrigerant quantity judgment: significantly insufficient | p.81 |
| d37 | V8S outdoor (status) | Indoor unit connected to the system is not common | p.81 |
| d38 | V8S outdoor (status) | Too low proportion of running indoor units | p.81 |
| d39 | V8S outdoor (status) | Failed to detect refrigerant amount during backup | p.81 |
| d42 | V8S outdoor (status) | Communication error between the outdoor unit and the optional board | p.81 |
| A01 | V8 indoor | Emergency stop | p.66 |
| C52 | V8 indoor | Abnormal communication between the indoor unit and Wi-Fi Kit | p.66 |
| A11 | V8 indoor | R32 refrigerant leaks, requiring shutdown immediately | p.66 |
| C61 | V8 indoor | Abnormal communication between the indoor unit main control board and display board | p.66 |
| A51 | V8 indoor | Outdoor unit fault | p.66 |
| C71 | V8 indoor | Abnormal communication between the AHU Kit slave unit and master unit | p.66 |
| A71 | V8 indoor | Interlocking control Heat Recovery Ventilation Unit fault(in-series application) | p.66 |
| C72 | V8 indoor | Number of AHU Kits is not the same as the set number | p.66 |
| A72 | V8 indoor | The Humidity Unit fault | p.66 |
| C73 | V8 indoor | Abnormal communication between the linked humidifying indoor unit and master indoor unit | p.66 |
| A73 | V8 indoor | Interlocking control Heat Recovery Ventilation Unit fault(non-serial application) | p.66 |
| C74 | V8 indoor | Abnormal communication between the linked FAPU and master indoor unit (series setting) | p.66 |
| A74 | V8 indoor | The AHU Kit slave unit fault | p.66 |
| C75 | V8 indoor | Abnormal communication between the linked FAPU and master indoor unit (non-series setting) | p.66 |
| A81 | V8 indoor | Self-check fault | p.66 |
| C76 | V8 indoor | Abnormal communication between the main wired controller and secondary wired controller | p.66 |
| A82 | V8 indoor | MS (refrigerant flow direction switching device) fault | p.66 |
| C77 | V8 indoor | Abnormal communication between the indoor unit main control board and 1# Expansion board | p.66 |
| A91 | V8 indoor | Mode conflict | p.66 |
| C78 | V8 indoor | Abnormal communication between the indoor unit main control board and 2# Expansion board | p.66 |
| b11 | V8 indoor | 1# EEV coil fault | p.66 |
| C79 | V8 indoor | Abnormal communication between the indoor unit main control board and Switch module | p.66 |
| b12 | V8 indoor | 1# EEV body fault | p.66 |
| C81 | V8 indoor | The indoor unit is in a power-off state | p.66 |
| b13 | V8 indoor | 2# EEV coil fault | p.66 |
| d16 | V8 indoor | Air inlet temperature of the indoor unit is too low in heating mode | p.66 |
| b14 | V8 indoor | 2# EEV body fault | p.66 |
| d17 | V8 indoor | Air inlet temperature of the indoor unit is too high in cooling mode | p.66 |
| d50 | V8 indoor | AHU kit fan running status input signal exception | p.66 |
| b34 | V8 indoor | Protection on 1# water pump | p.66 |
| d81 | V8 indoor | Alarm for exceeding temperature and humidity range | p.66 |
| b35 | V8 indoor | Protection on 2# water pump | p.66 |
| dE1 | V8 indoor | Sensor control board fault | p.66 |
| b36 | V8 indoor | Water level switch alarm | p.66 |
| dE2 | V8 indoor | PM2.5 sensor fault | p.66 |
| b71 | V8 indoor | Reheating electric heater fault | p.66 |
| dE3 | V8 indoor | CO2 sensor fault | p.66 |
| b72 | V8 indoor | Preprocessing electric heater fault | p.66 |
| dE4 | V8 indoor | Formaldehyde sensor fault | p.66 |
| b81 | V8 indoor | Humidifier fault | p.66 |
| dE5 | V8 indoor | Human Detect sensor fault | p.66 |
| C11 | V8 indoor | Duplicate indoor unit address code | p.66 |
| E21 | V8 indoor | T0 (fresh inlet air temperature sensor) short-circuits or cuts off | p.66 |
| C21 | V8 indoor | Abnormal communication between the indoor unit and outdoor unit | p.66 |
| E22 | V8 indoor | The upper dry bulb temperature sensor short-circuits or cuts off | p.66 |
| C41 | V8 indoor | Abnormal communication between the indoor unit main control board and fan drive board | p.66 |
| E23 | V8 indoor | The lower dry bulb temperature sensor short-circuits or cuts off | p.66 |
| C51 | V8 indoor | Abnormal communication between the indoor unit and wired controller | p.66 |
| E24 | V8 indoor | T1 (indoor unit return air temperature sensor) short-circuits or cuts off | p.66 |
| E31 | V8 indoor | Wired controller temperature sensor failure | p.67 |
| U01 | V8 indoor | Locked (electronic lock) | p.67 |
| E32 | V8 indoor | The wireless temperature sensor short-circuits or cuts off | p.67 |
| U11 | V8 indoor | Unit model code not set | p.67 |
| E33 | V8 indoor | The external room temperature sensor short-circuits or cuts off | p.67 |
| U12 | V8 indoor | Capacity(HP) code not set | p.67 |
| E61 | V8 indoor | Tcp (pre-cooled fresh air temperature sensor) short- circuits or cuts off | p.67 |
| U14 | V8 indoor | The capacity value of the AHU Kit DIP switch does not match the model | p.67 |
| E62 | V8 indoor | Tph (pre-heated fresh air temperature sensor) short- circuits or cuts off | p.67 |
| U15 | V8 indoor | The DIP value of AHU Kit's fan speed output voltage is incorrect | p.67 |
| E81 | V8 indoor | TA (outlet air temperature sensor) short-circuits or cuts off | p.67 |
| U26 | V8 indoor | Mismatch between indoor unit model and outdoor unit model | p.67 |
| EA1 | V8 indoor | Outlet air humidity sensor fault | p.67 |
| U38 | V8 indoor | Address code not detected | p.67 |
| EA2 | V8 indoor | Return air humidity sensor fault | p.67 |
| J01 | V8 indoor | Motor failed more than once | p.67 |
| EA3 | V8 indoor | Upper wet bulb sensor fault | p.67 |
| J1E | V8 indoor | IPM (fan module) overcurrent protection | p.67 |
| EA4 | V8 indoor | Lower wet bulb sensor fault | p.67 |
| J11 | V8 indoor | Instantaneous overcurrent protection for phase current | p.67 |
| EC1 | V8 indoor | R32 refrigerant leakage sensor fault | p.67 |
| J3E | V8 indoor | Low bus voltage fault | p.67 |
| F01 | V8 indoor | T2A (heat exchanger liquid pipe temperature sensor) short-circuits or cuts off | p.67 |
| J31 | V8 indoor | High bus voltage fault | p.67 |
| F11 | V8 indoor | T2 (heat exchanger middle temperature sensor) short- circuits or cuts off | p.67 |
| J43 | V8 indoor | Phase current sample bias error | p.67 |
| F12 | V8 indoor | T2 (heat exchanger middle temperature sensor) over temperature protection | p.67 |
| J45 | V8 indoor | Motor and indoor unit are unmatched | p.67 |
| F21 | V8 indoor | T2B (heat exchanger gas pipe temperature sensor) short-circuits or cuts off | p.67 |
| J47 | V8 indoor | IPM and indoor unit are unmatched | p.67 |
| P71 | V8 indoor | Main control board EEPROM fault | p.67 |
| J5E | V8 indoor | Motor startup failure | p.67 |
| P72 | V8 indoor | Indoor unit display control board EEPROM fault | p.67 |
| J52 | V8 indoor | Motor blocking protection | p.67 |
| P31/P34 | V8 indoor | Fan drive board AC side overcurrent protection | p.67 |
| J55 | V8 indoor | Speed control mode setting error | p.67 |
| P52 | V8 indoor | The voltage of the power supply is too low | p.67 |
| J6E | V8 indoor | Phase lack protection of motor | p.67 |
| d0 | V8 indoor (status) | Oil return or preheating operation | p.67 |
| d61 | V8 indoor (status) | Remote shutdown | p.67 |
| dC | V8 indoor (status) | Self-cleaning | p.67 |
| d71 | V8 indoor (status) | Indoor unit backup operation | p.67 |
| dd | V8 indoor (status) | Mode conflict | p.67 |
| d72 | V8 indoor (status) | Outdoor unit backup operation | p.67 |
| dF | V8 indoor (status) | Defrosting | p.67 |
| OTA | V8 indoor (status) | Main control program upgrading | p.67 |
| d51 | V8 indoor (status) | Initial static pressure detection | p.67 |
| dH | V8 indoor (status) | Hot water mode(Specific series) | p.67 |
| C0 | Atom T | Communication fault between Inverter module Board and communication terminals block | p.44 |
| U2 | Atom T | System combination error | p.44 |
| E2 | Atom T | Communication error between indoor and outdoor unit | p.44 |
| E4 | Atom T | T3 or T4 temperature sensor fault | p.44 |
| E5 | Atom T | Input voltage protection | p.44 |
| E6 | Atom T | DC fan protection | p.44 |
| Eb | Atom T | E6 fault occurs more than six times in an hour. | p.44, manual restart |
| E9 | Atom T | EEPROM Error | p.44, manual restart |
| E.9. | Atom T | Compressor parameters mismatch | p.44, manual restart |
| EF | Atom T | PFC feedback resistance failure protection | p.44, manual restart |
| EH | Atom T | Refrigerant radiator temperature sensor fault | p.44 |
| EP | Atom T | Cooling ambient temperature lower than -16℃ | p.44 |
| F1 | Atom T | DC bus voltage protection | p.44 |
| H4 | Atom T | L0 fault occurs three times in one hour. | p.44 |
| H7 | Atom T | The number of online indoor units have decreased/increased | p.44 |
| PL | Atom T | Radiator surface temperature protection | p.44 |
| P1 | Atom T | System high pressure protection | p.44 |
| P2 | Atom T | System low pressure protection | p.44 |
| P3 | Atom T | Overcurrent protection | p.44 |
| P5 | Atom T | Outdoor condenser temperature T3 protection | p.44 |
| P9 | Atom T | Poor reversing of four-way valve | p.44, manual restart |
| PE | Atom T | Indoor unit evaporator temperature T2 protection | p.44 |
| Ph | Atom T | Abnormal condensation protection | p.44 |
| Pd | Atom T | Anti-condensation protection | p.44, manual restart |
| L0 | Atom T | IPM module protection | p.44, manual restart |
| L1 | Atom T | DC generatrix low voltage protection | p.44, manual restart |
| L2 | Atom T | DC generatrix high voltage protection | p.44, manual restart |
| L3 | Atom T | Other driving errors | p.44, manual restart |
| L4 | Atom T | Overcurrent, Loss speed protection | p.44, manual restart |
| L5 | Atom T | Zero speed protection | p.44, manual restart |
| L7 | Atom T | Compressor phase lost protection | p.44, manual restart |
| P4 | Atom T | Discharge temperature protection | p.67 |
| L8 | Atom T | L category of inverter module protection | p.77 |
| L9 | Atom T | L category of inverter module protection | p.77 |
| E0 | V5 heat recovery | Communication error between outdoor units | p.157 |
| E1 | V5 heat recovery | Phase sequence error | p.157 |
| E2 | V5 heat recovery | Communication error between indoor units and the master unit | p.157 |
| E4 | V5 heat recovery | Outdoor ambient temperature sensor (T4) and condenser pipe temperature sensor (T3/T5) error | p.157 |
| E5 | V5 heat recovery | Power voltage error | p.157 |
| E7 | V5 heat recovery | Discharge temperature sensor error | p.157 |
| E8 | V5 heat recovery | Outdoor unit address is wrong | p.157 |
| xE9 | V5 heat recovery | Driver model is mismatching | p.157 |
| H0 | V5 heat recovery | Communication error between main control chip and inverter driver chip | p.157 |
| H1 | V5 heat recovery | Communication error between main control chip and communication chip | p.157 |
| H2 | V5 heat recovery | Quantity of outdoor units decreased | p.157 |
| H3 | V5 heat recovery | Quantity of outdoor units increased | p.157 |
| H4 | V5 heat recovery | P6 protection appears three times in 60 minutes | p.157 |
| H5 | V5 heat recovery | P2 protection appears three times in 60 minutes | p.157 |
| H6 | V5 heat recovery | P4 protection appears three times in 100 minutes | p.157 |
| H7 | V5 heat recovery | Quantity of indoor units decreased | p.157 |
| H8 | V5 heat recovery | High pressure sensor error | p.157 |
| H9 | V5 heat recovery | P9 protection appears three times in 60 minutes | p.157 |
| xHd | V5 heat recovery | Slave unit malfunction | p.157 |
| C7 | V5 heat recovery | PL protection appears three times in 100 minutes | p.157 |
| P1 | V5 heat recovery | High pressure protection | p.157 |
| P2 | V5 heat recovery | Low pressure protection | p.157 |
| xP3 | V5 heat recovery | Over current protection of inverter compressor | p.157 |
| P4 | V5 heat recovery | Compressor discharge temperature protection | p.157 |
| P5 | V5 heat recovery | Condenser high temperature protection | p.157 |
| xP6 | V5 heat recovery | Inverter module protection | p.157 |
| P9 | V5 heat recovery | Fan module protection | p.157 |
| PL | V5 heat recovery | Temperature protection of main inverter module | p.157 |
| L0 | V5 heat recovery | Inverter module error | p.157 |
| L1 | V5 heat recovery | DC bus low voltage error | p.158 |
| L2 | V5 heat recovery | DC bus high voltage error | p.158 |
| L4 | V5 heat recovery | MCE error, synchronisation or closed loop | p.158 |
| L5 | V5 heat recovery | Zero speed protection | p.158 |
| L7 | V5 heat recovery | Phase sequence error | p.158 |
| L8 | V5 heat recovery | Frequency difference of more than 15 Hz within one second | p.158 |
| L9 | V5 heat recovery | Difference of more than 15 Hz between the real and the set frequency | p.158 |
Run Midea on AirNexus
AirNexus supplies the controls and your HVAC contractor installs them. One app covers every unit on the site.
Not sure which fits? Find your system. AirNexus supplies Australia and New Zealand; distributors and project teams elsewhere can register as a partner.
Sources
The code meanings in this guide are drawn from the following Midea service manuals.
- Midea V8S Series VRF Service Manual (MV8S-252WV2GN1 to MV8S-670WV2GN1), 14 March 2024, V1, Part 6 error code tables
- Midea V8 VRF Indoor Units Service Manual, 24 May 2024, section 7 Errors and operation code
- Midea ATOM T Series Mini VRF Service Manual, R32, 220-240 V 50 Hz, 3 January 2024, V1, Part 5 Diagnosis and Troubleshooting
- Midea MIV V5 Heat Recovery DC Inverter R410A Service Manual (DM14-01.01.18en), error code table
Midea fault codes: frequently asked questions
What does Midea VRF error code E1 mean?
It depends on the series. On Midea V5 heat recovery systems, E1 is a phase sequence error: it shows on the faulty unit and all outdoor units go to standby. The current V8 range uses three-character codes instead, and the Atom T mini VRF has no E1. See the V5 E1 entry.
What does Midea error code C21 mean?
On the V8 range, C21 is a communication error between an indoor unit and the master outdoor unit. The V8 indoor unit manual lists it as abnormal communication between the indoor and outdoor unit. See the C21 entry.
What does Midea error code P3 mean?
On an Atom T mini VRF, P3 is overcurrent protection. On a V5 heat recovery system, the manual lists it as xP3: over current protection of the inverter compressor. Check the series on the outdoor unit label. See the Atom T P3 entry.
Can I see Midea fault codes remotely?
Yes. A Nexus 8, 16 or 32 on the Midea central control line sends each fault to the free AirNexus app as a push notification, with the unit address and the time it happened. Nexus iQ lists it in Findings & Insights, and the Diagnostics view shows the system’s live readings around it. See VRF control.