Gree GMV Systems: How the Codes Read
Gree GMV systems show a fault as a two-character code on the outdoor unit’s main board display, the indoor wired controller and the indoor display receiver. The GMV6 service manual sorts its codes into four groups: indoor unit codes (L, d, y and o), outdoor unit codes (E, F, J, b, P, H and G), system and commissioning codes (C and U) and status codes (A and n) that report what the system is doing rather than a fault.
Two things save time on site. First, compressor and fan drive faults are read in two steps: when the wired controller shows P0, P1 or P2 (compressor drive) or H0 or H1 (fan drive), the 2-digit display on the outdoor main board shows the exact code, such as P5, P8 or PJ. Second, status codes are not faults: A3 (defrosting) and A4 (oil return in heating mode) can stop the indoor fan for 5 to 10 minutes, and A0 shows until commissioning is complete. When troubleshooting a modular system, the manual says to power every outdoor unit off and on at the same time, never just some of them.
This guide covers the Gree GMV6 VRF codes in Gree’s GMV6 DC Inverter VRF Units Service Manual (GC202005-I): all 218 fault codes and 37 status codes. Every meaning below comes from the manual, with the manual page so you can go straight to the full troubleshooting steps. Gree residential split system codes are a different list and are not covered here.
Search all 255 Gree codes · Run Gree on AirNexus
Communication and System Setup Faults (C0, C2, C4)
Most C codes come back to the communication cables, the master and address DIP switches or the number of units the system expects to see. U codes are raised during commissioning and setup.
- Communication cables are connected wrongly or get loose
- Communication cables are broken
- Poor contact of communication cables
- Number of wired controllers connected or addresses are set improperly
- Controller operates improperly
- The communication cables between the main board of outdoor unit and inverter compressor driver inside the module are connected improperly
- The inverter compressor driver operates improperly
- The main board operates improperly
- The communication cables between the main board of outdoor unit and inverter fan driver inside the module are connected improperly
- The inverter fan driver operates improperly
- The main board operates improperly
- Poor contact of communication cables
- The indoor units are powered off
- The main board of indoor unit operates improperly
- The same engineering SN is configured for different indoor units
- The main board of indoor unit is from another unit
- Abnormal communication among modules
- The modules are not powered on
- The master DIP switch is abnormal and no master unit exists in the network
- The communication cables are abnormal, causing the master unit to be disconnected
- Abnormal detection circuit
- The master DIP switch is abnormal and multiple master units exist in the network
- Abnormal detection circuit
- If two or more master units' DIP switches (SA2) are detected to be master unit's DIP switches, keep only one master unit's DIP switch (SA2) to be "00000" and other master units' DIP switches (SA2) to be different
- Abnormal DIP switch or main board
- The total rated capacity of the indoor units exceeds 1.35 times of the total rated capacity of the outdoor units
- Capacity DIP switch error or jumper cap error (for some models without jumper caps, jumper cap error is not detected)
- DIP switch or jumper cap is broken
- Abnormal detection circuit
- The power is connected wrongly or phase loss or reverse phase occurs
- Abnormal detection circuit
- The check valve of the outdoor unit is not open
Know about C0 before the tenant does.
A Nexus controller sits on the system's control network and logs every fault the moment it happens: the code, the unit address, and the time. It lands in the AirNexus app before anyone calls you.
Pressure and Temperature Protection (E1, E3, E4)
The protection stops. Each one has a clear trip point in the manual, listed under the entry.
- Check valve of the outdoor unit is closed
- Abnormal high pressure sensor
- The high pressure switch operates improperly
- Abnormal outdoor or indoor fans
- Clogging of indoor filter or air duct (heating mode)
- The ambient temperature where the unit operates is too high
- Excessive refrigerant in the unit
- Clogging of unit pipes
- The compressor's temperature sensor for air discharge operates improperly
- The electronic expansion valve of indoor unit operates improperly in cooling mode
- The electronic expansion valve of outdoor unit operates improperly in heating mode
- Excessive refrigerant in the unit
- Check valve of the outdoor unit is closed
- Abnormal low pressure sensor
- Abnormal outdoor or indoor fans
- Clogging of indoor filter or air duct (cooling mode)
- The ambient temperature where the unit operates is too low
- Insufficient refrigerant in the unit
- Clogging of unit pipes
- Check valve of the outdoor unit is closed
- The electronic expansion valve operates improperly
- Abnormal outdoor or indoor fans
- Clogging of indoor filter or air duct (cooling mode)
- The ambient temperature where the unit operates exceeds the limit
- Insufficient refrigerant in the unit
- Clogging of unit pipes
- Insufficient refrigerant in the unit
- The pipes leak
- The coil or connecting wire is abnormal
- The main board is abnormal
- The four-way valve is abnormal
- The pressure sensor is abnormal
- The ambient temperature where the unit operates exceeds the limit
- The pressure sensor is abnormal
- The ambient temperature where the unit operates exceeds the limit
Compressor and Fan Drive Faults (P0, P1, P5, P8)
Drive faults are read in two steps: the wired controller shows a group code (P0, P1 or P2 for the compressor drive, H0 or H1 for the fan drive) and the 2-digit display on the outdoor main board shows the exact code.
- Compressor drive module reset protection (outdoor board shows P3)
- Temperature sensor fault of compressor drive (outdoor board shows P7)
- IPM over temperature protection for the compressor drive (outdoor board shows P8)
- Current detection circuit fault of compressor drive (outdoor board shows PC)
- Charging loop fault of compressor drive (outdoor board shows PF)
- Loss of synchronization protection for the inverter compressor (outdoor board shows P9)
- Inverter compressor startup failure (outdoor board shows PJ)
- Inverter compressor over-current protection (outdoor board shows P5)
- IPM module protection for the compressor drive (outdoor board shows P6)
- Communication fault of compressor drive (outdoor board shows C2)
- Poor contact of compressor's UVW cables
- The compressor's UVW cables are wrongly connected
- The compressor is damaged
- The system is blocked
- IPM module of the compressor drive board is damaged
- Poor contact of compressor's UVW cables
- The compressor's UVW cables are wrongly connected
- The compressor is damaged
- The system is blocked
- IPM module of the compressor drive board is damaged
- The IPM module's screws are not tightened
- The IPM module is not covered, or unevenly covered by thermal grease, or covered by dried thermal grease
- The compressor drive board operates improperly
- The compressor drive board operates improperly
- The compressor is damaged
- The unit's input power cable has a voltage exceeding 460 V
- The compressor drive board operates improperly
- The unit's input power cable has a voltage below 320V
- The compressor drive board operates improperly
- Poor contact of compressor's UVW cables
- The compressor is damaged
- The compressor drive board operates improperly
- The unit's parameters are abnormal
- The drive module is abnormal
- The compressor is abnormal
- Poor contact of fan's UVW cables
- The fan is damaged
- The blades are stuck (the blades are blocked or the motor shaft gets rusty)
- The fan drive board operates improperly
- Poor contact of fan's UVW cables
- The fan is damaged
- The blades are stuck (the blades are blocked or the motor shaft gets rusty)
- The fan drive board operates improperly
- Poor contact of fan's UVW cables
- The fan is damaged
- The blades are stuck (the blades are blocked or the motor shaft gets rusty)
- The fan drive board operates improperly
Outdoor Board and Sensor Faults (F and b Codes)
Most outdoor sensor faults are raised when the reading is out of range for 30 seconds in a row (FH, the compressor 1 current sensor, after 3 seconds). F0 is the outdoor main board itself.
- Abnormal address chip
- Abnormal memory chip
- Abnormal clock chip
- Poor contact between the high pressure sensor and the main board interface
- Poor contact between high pressure sensor and part where the pressure is detected
- Abnormal high pressure sensor
- Abnormal sensor detection circuit
- Poor contact between the low pressure sensor and the main board interface
- Poor contact between low pressure sensor and part where the pressure is detected
- Abnormal low pressure sensor
- Abnormal low pressure sensor detection circuit
- Poor contact between the discharge temperature sensor and the main board interface
- Abnormal discharge temperature sensor
- Abnormal detection circuit
- Poor contact between the circuit sensor and the main board interface
- Abnormal small board of circuit sensor
- Abnormal detection circuit
- Poor contact between the temperature sensor and the main board interface
- Abnormal temperature sensor
- Abnormal detection circuit
Indoor Unit Faults (L and d Codes)
Indoor unit faults show on the wired controller and the indoor display receiver.
- The indoor unit is faulty
- The motor stops or is stuck
- The main board of indoor unit operates improperly
- The indoor unit is installed improperly
- The drain pump is damaged
- The float switch operates improperly
- The main board of indoor unit operates improperly
- The wires of the wired controller are short circuited
- The main board of indoor unit operates improperly
- The main board of the wired controller is abnormal
- The indoor filter and evaporator are dirty
- The indoor motor is stuck
- Insufficient refrigerant in the unit
- The ambient temperature where the indoor unit and outdoor unit operate is too low
- More than 16 indoor units are connected to one wired controller
- The number of indoor units connected to the wired controller is not the same as what is configured under integrated control
- The indoor unit is incompatible with the outdoor unit
- Abnormal address chip
- Abnormal memory chip
- Poor contact between the ambient temperature sensor and the main board interface
- Abnormal ambient temperature sensor
- Abnormal detection circuit
- Poor contact between the inlet pipe temperature sensor and the main board interface
- Abnormal inlet pipe temperature sensor
- Abnormal detection circuit
- Poor contact between the outlet pipe temperature sensor and the main board interface
- Abnormal outlet pipe temperature sensor
- Abnormal detection circuit
What Nexus iQ Shows Alongside the Code
A fault code tells you what tripped. On a Nexus 8, 16 or 32, Nexus iQ reads the Gree system’s own data off its control line, so you can see the readings around a code before anyone goes to site. What you see depends on what the system reports.
| When you see | The code tells you | In Nexus iQ |
|---|---|---|
| C0, C4 | A unit has stopped talking to the system | Push notification with the unit address and time. Diagnostics marks a reading that has stopped updating as stale, with its age. |
| E1, J8 | High pressure or pressure ratio tripped | High and low pressure live in Diagnostics, charted in Trends from 6 hours to 30 days. |
| E4 | Compressor discharge temperature over 118°C | Discharge temperature live, charted in Trends to see what led up to the trip. |
| E3, U4 | Low pressure or refrigerant loss protection | Suction temperature and low pressure live, charted in Trends. |
| P5, P8, PJ | Compressor drive protection | Compressor frequency and power draw live, with a Health score per unit over 24 hours, 7 days or 30 days. |
The same faults reach the free AirNexus app as push notifications. See Nexus iQ.
Gree GMV Error Code List
Search by code or keyword. Codes with an entry above link to it. Status codes are greyed out: they report what the system is doing, not a fault.
| Code | Group | Meaning | Manual page |
|---|---|---|---|
| U0 | System setup | Preheat time of compressor is insufficient | p.71 |
| U2 | System setup | Wrong setting of ODU’s capacity code/jumper cap | p.71 |
| U3 | System setup | Power phase sequence protection | p.71 |
| U4 | System setup | Refrigerant-lacking protection | p.71 |
| U5 | System setup | Wrong address for driving board of compressor | p.71 |
| U6 | System setup | Alarm because valve is abnormal | p.71 |
| U8 | System setup | Malfunction of pipeline for IDU | p.71 |
| U9 | System setup | Malfunction of pipeline for ODU | p.71 |
| UC | System setup | Setting of main IDU is succeeded | p.71 |
| UL | System setup | Emergency operation DIP switch code of compressor is wrong | p.71 |
| UE | System setup | Charging of refrigerant is invalid | p.71 |
| UF | System setup | Identification malfunction of IDU of mode exchanger | p.71 |
| Ud | System setup | Drive board of grid-connection is abnormal | p.71 |
| Un | System setup | Communication malfunction between the drive board of grid-connection and the main board | p.71 |
| C0 | System setup | Communication malfunction between IDU, ODU and IDU’s wired controller | p.71 |
| C1 | System setup | Communication malfunction between main control and DC-DC controller | p.71 |
| C2 | System setup | Communication malfunction between main control and inverter compressor driver | p.71 |
| C3 | System setup | Communication malfunction between main control and inverter fan driver | p.71 |
| C4 | System setup | Malfunction of lack of IDU | p.71 |
| C5 | System setup | Alarm because project code of IDU is inconsistent | p.71 |
| C6 | System setup | Alarm because ODU quantity is inconsistent | p.71 |
| C7 | System setup | Abnormal communication of converter | p.71 |
| C8 | System setup | Emergency status of compressor | p.71 |
| C9 | System setup | Emergency status of fan | p.71 |
| CA | System setup | Emergency status of module | p.71 |
| CH | System setup | Rated capacity is too high | p.71 |
| CC | System setup | No main unit | p.71 |
| CL | System setup | The matching ratio of rated capacity for IDU and ODU is too low | p.71 |
| CE | System setup | Communication malfunction between mode exchanger and IDU | p.71 |
| CF | System setup | Malfunction of multiple main control units | p.71 |
| CJ | System setup | Address DIP switch code of system is shocking | p.71 |
| CP | System setup | Malfunction of multiple wired controller | p.71 |
| CU | System setup | Communication malfunction between IDU and the receiving lamp | p.71 |
| Cb | System setup | Overflow distribution of IP address | p.71 |
| Cd | System setup | Communication malfunction between mode exchanger and ODU | p.71 |
| Cn | System setup | Malfunction of network for IDU and ODU of mode exchanger | p.71 |
| Cy | System setup | Communication malfunction of mode exchanger | p.71 |
| E0 | Outdoor unit | Malfunction of ODU | p.69 |
| E1 | Outdoor unit | High-pressure protection | p.69 |
| E2 | Outdoor unit | Discharge low-temperature protection | p.69 |
| E3 | Outdoor unit | Low-pressure protection | p.69 |
| E4 | Outdoor unit | High discharge temperature protection of compressor | p.69 |
| Ed | Outdoor unit | Drive IPM low temperature protection | p.69 |
| F0 | Outdoor unit | Main board of ODU is poor | p.69 |
| F1 | Outdoor unit | Malfunction of high-pressure sensor | p.69 |
| F3 | Outdoor unit | Malfunction of low-pressure sensor | p.69 |
| F5 | Outdoor unit | Malfunction of discharge temperature sensor of compressor 1 | p.69 |
| F6 | Outdoor unit | Malfunction of discharge temperature sensor of compressor 2 | p.69 |
| F7 | Outdoor unit | Malfunction of discharge temperature sensor of compressor 3 | p.69 |
| F8 | Outdoor unit | Malfunction of discharge temperature sensor of compressor 4 | p.69 |
| F9 | Outdoor unit | Malfunction of discharge temperature sensor of compressor 5 | p.69 |
| FA | Outdoor unit | Malfunction of discharge temperature sensor of compressor 6 | p.69 |
| FC | Outdoor unit | Current sensor of compressor 2 is abnormal | p.69 |
| FL | Outdoor unit | Current sensor of compressor 3 is abnormal | p.69 |
| FE | Outdoor unit | Current sensor of compressor 4 is abnormal | p.69 |
| FF | Outdoor unit | Current sensor of compressor 5 is abnormal | p.69 |
| FJ | Outdoor unit | Current sensor of compressor 6 is abnormal | p.69 |
| FP | Outdoor unit | Malfunction of DC motor | p.69 |
| FU | Outdoor unit | Malfunction of casing top temperature sensor of compressor 1 | p.69 |
| Fb | Outdoor unit | Malfunction of casing top temperature sensor of compressor 2 | p.69 |
| Fd | Outdoor unit | Malfunction of exit tube temperature sensor of mode exchanger | p.69 |
| Fn | Outdoor unit | Malfunction of inlet tube temperature sensor of mode exchanger | p.69 |
| J0 | Outdoor unit | Protection for other modules | p.69 |
| J1 | Outdoor unit | Over-current protection of compressor 1 | p.69 |
| J2 | Outdoor unit | Over-current protection of compressor 2 | p.69 |
| J3 | Outdoor unit | Over-current protection of compressor 3 | p.69 |
| J4 | Outdoor unit | Over-current protection of compressor 4 | p.69 |
| J5 | Outdoor unit | Over-current protection of compressor 5 | p.69 |
| J6 | Outdoor unit | Over-current protection of compressor 6 | p.69 |
| J7 | Outdoor unit | Gas-mixing protection of 4-way valve | p.69 |
| J8 | Outdoor unit | High pressure ratio protection of system | p.69 |
| J9 | Outdoor unit | Low pressure ratio protection of system | p.69 |
| JA | Outdoor unit | Protection because of abnormal pressure | p.69 |
| JC | Outdoor unit | Water flow switch protection | p.69 |
| JL | Outdoor unit | Protection because high pressure is too low | p.69 |
| JE | Outdoor unit | Oil-return pipe is blocked | p.69 |
| JF | Outdoor unit | Oil-return pipe is leaking | p.69 |
| b1 | Outdoor unit | Malfunction of outdoor ambient temperature sensor | p.69 |
| b2 | Outdoor unit | Malfunction of defrosting temperature sensor 1 | p.69 |
| b3 | Outdoor unit | Malfunction of defrosting temperature sensor 2 | p.69 |
| b4 | Outdoor unit | Malfunction of liquid outlet temperature sensor of sub-cooler | p.69 |
| b5 | Outdoor unit | Malfunction of gas outlet temperature sensor of sub-cooler | p.69 |
| b6 | Outdoor unit | Malfunction of inlet tube temperature sensor of vapor liquid separator | p.69 |
| b7 | Outdoor unit | Malfunction of exit tube temperature sensor of vapor liquid separator | p.69 |
| b8 | Outdoor unit | Malfunction of outdoor humidity sensor | p.69 |
| b9 | Outdoor unit | Malfunction of gas temperature sensor of heat exchanger | p.69 |
| bA | Outdoor unit | Malfunction of oil-return temperature sensor 1 | p.69 |
| bH | Outdoor unit | Clock of system is abnormal | p.69 |
| bE | Outdoor unit | Malfunction of inlet tube temperature sensor of condenser | p.69 |
| bF | Outdoor unit | Malfunction of outlet tube temperature sensor of condenser | p.69 |
| bJ | Outdoor unit | High-pressure sensor and low-pressure sensor are connected reversely | p.69 |
| bP | Outdoor unit | Malfunction of temperature sensor of oil-return 2 | p.69 |
| bU | Outdoor unit | Malfunction of temperature sensor of oil return 3 | p.69 |
| bb | Outdoor unit | Malfunction of temperature sensor of oil return 4 | p.69 |
| bd | Outdoor unit | Malfunction of gas inlet temperature sensor of sub-cooler | p.69 |
| bn | Outdoor unit | Malfunction of liquid inlet temperature sensor of sub-cooler | p.69 |
| P0 | Outdoor unit | Malfunction of driving board of compressor | p.69 |
| P1 | Outdoor unit | Driving board of compressor operates abnormally | p.69 |
| P2 | Outdoor unit | Voltage protection of driving board power of compressor | p.69 |
| P3 | Outdoor unit | Reset protection of driving module of compressor | p.69 |
| P4 | Outdoor unit | Drive PFC protection of compressor | p.69 |
| P5 | Outdoor unit | Over-current protection of inverter compressor | p.70 |
| P6 | Outdoor unit | Drive IPM module protection of compressor | p.70 |
| P7 | Outdoor unit | Malfunction of drive temperature sensor of compressor | p.70 |
| P8 | Outdoor unit | Drive IPM high temperature protection of compressor | p.70 |
| P9 | Outdoor unit | Desynchronizing protection of inverter compressor | p.70 |
| PA | Outdoor unit | Malfunction of drive storage chip of compressor | p.70 |
| PH | Outdoor unit | High-voltage protection of compressor’s drive DC bus bar | p.70 |
| PC | Outdoor unit | Malfunction of current detection circuit drive of compressor | p.70 |
| PL | Outdoor unit | Low voltage protection for DC bus bar of drive of compressor | p.70 |
| PE | Outdoor unit | Phase-lacking of inverter compressor | p.70 |
| PF | Outdoor unit | Malfunction of charging loop of driven of compressor | p.70 |
| PJ | Outdoor unit | Failure startup of inverter compressor | p.70 |
| PP | Outdoor unit | AC current protection of inverter compressor | p.70 |
| PU | Outdoor unit | AC input voltage of drive of inverter compressor | p.70 |
| H0 | Outdoor unit | Malfunction of driving board of fan | p.70 |
| H1 | Outdoor unit | Driving board of fan operates abnormally | p.70 |
| H2 | Outdoor unit | Voltage protection of driving board power of fan | p.70 |
| H3 | Outdoor unit | Reset protection of driving module of fan | p.70 |
| H4 | Outdoor unit | Drive PFC protection of fan | p.70 |
| H5 | Outdoor unit | Over-current protection of inverter fan | p.70 |
| H6 | Outdoor unit | Drive IPM module protection of fan | p.70 |
| H7 | Outdoor unit | Malfunction of drive temperature sensor of fan | p.70 |
| H8 | Outdoor unit | Drive IPM high temperature protection of fan | p.70 |
| H9 | Outdoor unit | Desynchronizing protection of inverter fan | p.70 |
| HA | Outdoor unit | Malfunction of drive storage chip of inverter outdoor fan | p.70 |
| HH | Outdoor unit | High-voltage protection of fan’s drive DC bus bar | p.70 |
| HC | Outdoor unit | Malfunction of current detection circuit of fan drive | p.70 |
| HL | Outdoor unit | Low voltage protection of bus bar of fan drive | p.70 |
| HE | Outdoor unit | Phase-lacking of inverter fan | p.70 |
| HF | Outdoor unit | Malfunction of charging loop of fan drive | p.70 |
| HJ | Outdoor unit | Failure startup of inverter fan | p.70 |
| HP | Outdoor unit | AC current protection of inverter fan | p.70 |
| HU | Outdoor unit | AC input voltage of drive of inverter fan | p.70 |
| G0 | Outdoor unit | PV reversed connection protection | p.70 |
| G1 | Outdoor unit | PV anti-islanding protection | p.70 |
| G2 | Outdoor unit | PV DC overcurrent protection | p.70 |
| G3 | Outdoor unit | PV power generation overload | p.70 |
| G4 | Outdoor unit | PV leakage current protection | p.70 |
| G5 | Outdoor unit | Phase-lacking protection at power grid side | p.70 |
| G6 | Outdoor unit | PV LVRT | p.70 |
| G7 | Outdoor unit | Grid over/under frequency protection | p.70 |
| G8 | Outdoor unit | Overcurrent protection at power grid side | p.70 |
| G9 | Outdoor unit | Drive IPM module protection at power grid side | p.70 |
| GA | Outdoor unit | Low/high input voltage protection at power grid side | p.70 |
| GH | Outdoor unit | Photovoltaic DC/DC protection | p.70 |
| GC | Outdoor unit | Photovoltaic DC hardware overcurrent protection | p.70 |
| GL | Outdoor unit | Grid side hardware overcurrent protection | p.70 |
| GE | Outdoor unit | High or low photovoltaic voltage protection | p.70 |
| GF | Outdoor unit | DC bus neutral-point potential unbalance protection | p.70 |
| GJ | Outdoor unit | Grid side module high-temperature protection | p.70 |
| GP | Outdoor unit | Grid side temperature sensor protection | p.70 |
| GU | Outdoor unit | Charging circuit protection | p.70 |
| Gb | Outdoor unit | Grid side relay protection | p.70 |
| Gd | Outdoor unit | Grid side current side protection | p.70 |
| Gn | Outdoor unit | Insulation resistance protection | p.70 |
| Gy | Outdoor unit | Power protection (PV) | p.70 |
| FH | Outdoor unit | Abnormal Current Sensor of Compressor 1 | p.118 |
| L0 | Indoor unit | Malfunction of IDU | p.68 |
| L1 | Indoor unit | Protection of indoor fan | p.68 |
| L2 | Indoor unit | Auxiliary heating protection | p.68 |
| L3 | Indoor unit | Water-full protection | p.68 |
| L4 | Indoor unit | Abnormal Power for wired controller | p.68 |
| L5 | Indoor unit | Freeze prevention protection | p.68 |
| L6 | Indoor unit | Mode conflict | p.68 |
| L7 | Indoor unit | No main IDU | p.68 |
| L8 | Indoor unit | Power is insufficient | p.68 |
| L9 | Indoor unit | For single control over multiple units, number of IDU is inconsistent (HBS network) | p.68 |
| LA | Indoor unit | For single control over multiple units, IDU series is inconsistent (HBS network) | p.68 |
| LH | Indoor unit | Alarm due to bad air quality | p.68 |
| LC | Indoor unit | IDU is not matching with outdoor unit | p.68 |
| LL | Indoor unit | Malfunction of water flow switch | p.68 |
| LE | Indoor unit | Rotation speed of EC DC water pump is abnormal | p.68 |
| LF | Indoor unit | Malfunction of shunt valve setting | p.68 |
| LJ | Indoor unit | Setting of functional DIP switch code is wrong | p.68 |
| LP | Indoor unit | Zero-crossing malfunction of PG motor | p.68 |
| LU | Indoor unit | Zero-crossing malfunction of PG motor | p.68 |
| Lb | Indoor unit | For single control over multiple units, IDU is inconsistent (reheating-dehumidifying system) | p.68 |
| d1 | Indoor unit | Indoor PCB is poor | p.68 |
| d2 | Indoor unit | Malfunction of lower water temperature sensor of water tank | p.68 |
| d3 | Indoor unit | Malfunction of ambient temperature sensor | p.68 |
| d4 | Indoor unit | Malfunction of entry-tube temperature sensor | p.68 |
| d5 | Indoor unit | Malfunction of mid-tube temperature sensor | p.68 |
| d6 | Indoor unit | Malfunction of exit-tube temperature sensor | p.68 |
| d7 | Indoor unit | Malfunction of humidity sensor | p.68 |
| d8 | Indoor unit | Malfunction of water temperature sensor | p.68 |
| d9 | Indoor unit | Malfunction of jumper cap | p.68 |
| dA | Indoor unit | Web address of IDU is abnormal | p.68 |
| dH | Indoor unit | PCB of wired controller is abnormal | p.68 |
| dC | Indoor unit | Setting capacity of DIP switch code is abnormal | p.68 |
| dL | Indoor unit | Malfunction of air outlet temperature sensor | p.68 |
| dE | Indoor unit | Malfunction of indoor CO2 sensor | p.68 |
| dF | Indoor unit | Malfunction of upper water temperature sensor of water tank | p.68 |
| dJ | Indoor unit | Malfunction of backwater temperature sensor | p.68 |
| dP | Indoor unit | Malfunction of inlet tube temperature sensor of generator | p.68 |
| dU | Indoor unit | Malfunction of drainage pipe temperature sensor of generator | p.68 |
| db | Indoor unit | Debugging status | p.68 |
| dd | Indoor unit | Malfunction of solar power temperature sensor | p.68 |
| dn | Indoor unit | Malfunction of swing parts | p.68 |
| dy | Indoor unit | Malfunction of water temperature sensor | p.68 |
| y1 | Indoor unit | Malfunction of entry-tube temperature sensor 2 | p.68 |
| y2 | Indoor unit | Malfunction of exit-tube temperature sensor 2 | p.68 |
| y7 | Indoor unit | Malfunction of fresh air inlet temperature sensor | p.68 |
| y8 | Indoor unit | Malfunction of IDU’s air box sensor | p.68 |
| yA | Indoor unit | Malfunction of IFD | p.68 |
| o1 | Indoor unit | Low bus bar voltage of IDU | p.68 |
| o2 | Indoor unit | High bus bar voltage of IDU | p.68 |
| o3 | Indoor unit | IPM module protection of IDU | p.68 |
| o4 | Indoor unit | Failure startup of IDU | p.68 |
| o5 | Indoor unit | Over-current protection of IDU | p.68 |
| o6 | Indoor unit | Current detection circuit malfunction of IDU | p.68 |
| o7 | Indoor unit | Desynchronizing protection of IDU | p.68 |
| o8 | Indoor unit | Communication malfunction of IDU’s drive | p.68 |
| o9 | Indoor unit | Communication malfunction of main mater of IDU | p.68 |
| oA | Indoor unit | High temperature of IDU’s module | p.68 |
| ob | Indoor unit | Malfunction of temperature sensor of IDU’s module | p.68 |
| oC | Indoor unit | Charging circuit malfunction of IDU | p.68 |
| o0 | Indoor unit | Other drive malfunction | p.68 |
| A0 | Status (not a fault) | Unit waiting for debugging | p.71 |
| A2 | Status (not a fault) | Refrigerant recovery operation of after-sales | p.71 |
| A3 | Status (not a fault) | Defrosting | p.71 |
| A4 | Status (not a fault) | Oil-return | p.71 |
| A6 | Status (not a fault) | Heat pump function setting | p.71 |
| A7 | Status (not a fault) | Quiet mode setting | p.71 |
| A8 | Status (not a fault) | Vacuum pump mode | p.71 |
| AH | Status (not a fault) | Heating | p.71 |
| AC | Status (not a fault) | Cooling | p.70 |
| AL | Status (not a fault) | Charge refrigerant automatically | p.71 |
| AE | Status (not a fault) | Charge refrigerant manually | p.71 |
| AF | Status (not a fault) | Fan | p.71 |
| AJ | Status (not a fault) | Cleaning reminding of filter | p.71 |
| AP | Status (not a fault) | Debugging confirmation when starting up the unit | p.71 |
| AU | Status (not a fault) | Long-distance emergency stop | p.71 |
| Ab | Status (not a fault) | Emergency stop of operation | p.71 |
| Ad | Status (not a fault) | Limit operation | p.71 |
| An | Status (not a fault) | Child lock status | p.71 |
| Ay | Status (not a fault) | Shielding status | p.71 |
| n0 | Status (not a fault) | SE operation setting of system | p.71 |
| n3 | Status (not a fault) | Compulsory defrosting | p.71 |
| n4 | Status (not a fault) | Limit setting for max. capacity/output capacity | p.71 |
| n5 | Status (not a fault) | Compulsory excursion of engineering code of IDU | p.71 |
| n6 | Status (not a fault) | Inquiry of malfunction | p.71 |
| n7 | Status (not a fault) | Inquiry of parameters | p.71 |
| n8 | Status (not a fault) | Inquiry of project code of IDU | p.71 |
| n9 | Status (not a fault) | Check quantity of IDU on line | p.71 |
| nA | Status (not a fault) | Heat pump unit | p.71 |
| nH | Status (not a fault) | Heating only unit | p.71 |
| nC | Status (not a fault) | Cooling only unit | p.71 |
| nE | Status (not a fault) | Negative code | p.71 |
| nF | Status (not a fault) | Fan model | p.71 |
| nJ | Status (not a fault) | High temperature prevention when heating | p.71 |
| nU | Status (not a fault) | Eliminate the long-distance shielding command of IDU | p.71 |
| nb | Status (not a fault) | Bar code inquiry | p.71 |
| nn | Status (not a fault) | Length modification of connection pipe of ODU | p.71 |
| n2 | Status (not a fault) | Settings Status of Maximum Capacity Configuration Rate for Indoor and Outdoor Units | p.156 |
Run Gree on AirNexus
AirNexus supplies the controls and your HVAC contractor installs them. One app covers every unit on the site.
Not sure which fits? Find your system. AirNexus supplies Australia and New Zealand; distributors and project teams elsewhere can register as a partner.
Sources
The code meanings, detection conditions and causes in this guide are drawn from the following Gree service document.
Gree fault codes: frequently asked questions
What does Gree error code C0 mean?
On Gree GMV systems, C0 is a communication fault between the indoor and outdoor units, or between an indoor unit and its wired controller. The GMV6 service manual says it is raised after 30 seconds without communication, and points first to communication cables that are connected wrongly, loose, broken or making poor contact, then to the number of wired controllers or their address settings. See the C0 entry.
What does Gree error code E4 mean?
E4 is high discharge temperature protection for the compressor. The unit stops when the discharge temperature, measured on the discharge pipe and the top of the compressor, is above 118°C. The manual’s list starts with a closed outdoor unit valve, the electronic expansion valve, the indoor and outdoor fans, a clogged indoor filter or duct in cooling, and insufficient refrigerant. See the E4 entry.
Why does the wired controller show P1 when the outdoor unit shows P5?
Gree groups compressor drive faults. The wired controller shows P0, P1 or P2 and the 2-digit display on the outdoor main board shows the exact code: P5 (inverter compressor over-current) and P6 (IPM module protection) show as P1; P8 (IPM over temperature) and PJ (start-up failure) show as P0. Fan drive faults work the same way through H0 and H1. See the P1 entry.
Can I see Gree fault codes remotely?
Yes. A Nexus 8, 16 or 32 on the Gree central control line sends each fault to the free AirNexus app as a push notification, with the unit address and the time it happened. Nexus iQ lists it in Findings & Insights, and the Diagnostics view shows the system’s live readings around it. See VRF control.